I want to provide a 0/4-20mA powerfactor setpoint signal to easYgen-3000XT

Authors list
  • Justin Schneider

easYgens powerfactor angle is measured based on current L1 and between  voltage L1/L2 lines

You need to enter percentage values for power factor / cosphi  setpoints not absolute values. 

For example, if you want to have a setpoint from 0,80 capacitive (Capacitive loads are leading (current leads voltage)  to 0,20 inductive (inductive loads are lagging (current lags voltage) 

 you need to enter 40 for minimum and 90 for maximum value at the parameters for the used analog input.

1659421243992.png


Configuration of the AM on Setpoint page:

1674837292654.png


Configuration Analog input

1674839302519.png